Isolator for addressable systems
The Isolator is placed at intervals on the loop and ensures that, in the case of a short circuit, only the section between the isolators will be affected. When the short-circuit is removed, the isolators automatically restore power and data to the isolated section.
Technical data | |
Operating Voltage: | 17 to 28V DC |
Quiescent current | 35µA |
Dimensions: | 100mm diameter x 42 mm H (not in base). 50mm height when in base. |
Weigh: | 0,105 kg |
Operating temperature: | -20ºC to +60ºC |
Others: | On resistance 200000000Ω Requires a base 45681-211 |